An investigation was done by experts to determine the cause of the explosion. It is found that the most probable cause determined was the sudden introduction of feed water to the boiler due to low water in the boiler. Malfunction safety devices contributed to this occurence, which is by right can be avoided.
The recommendations made by these expert were ;
- Should develop procedures for the training and certification of all boileroperators.
- should invest in a remote monitoring system that will monitor the boileroperations while the boiler operators are performing their maintenance responsibilities.
- All maintenance to the boiler and boiler associated equipment’s controls and safety devicesshould be performed by an experienced and qualified outside vendor knowledgeable in theiroperation and function.
- Boilers and boiler associated equipment’s controls and safety devices should be testedannually by an experienced and qualified outside vendor knowledgeable in their operationand function.
- All steam pressure relief valves should be removed, inspected, and pressure tested annuallyto ensure proper nameplate set pressure and operation.
- It is crucial that all boiler operator daily operational tests, duties, and responsibilitiesrecommended by the boiler manufacturer are adhered to, followed, and performed.
- The audible and visual alarm system for the boiler plant should be overhauled to ensurenotification throughout the plant.
- Emergency and evacuation procedures should be developed.
- Should ensure that all mandatory inspections to the boilers are performedper the requirement of law.
- Any future incident or accident involving a boiler, pressure vessel (e.g., autoclave, air storagetank, etc.), or boiler related equipment should be reported to the govern authorities immediately.